Performance Data Sheet
RKA5513EXD
General Information
Model RKA5513EXD Refrigerant R-22
Test Condition ASHRAE Performance Test Voltage 230V ~ 60HZ
Return Gas 18.3°C (65°F) RETURN GAS Motor Type PSC
Performance Information
Condensing Temperature (°F)
Evap Temp (°F)
80 90 100 110 120 130 140
Btu/h 4860 4540
Watts 564 624
Amps 2.33 2.55
-15
Lb/h 62.4 60.8
Btu/h 5370 5030 4710
Watts 578 641 703
Amps 2.38 2.63 2.90
-10
Lb/h 68.7 67.0 65.4
Btu/h 5980 5610 5260 4920
Watts 593 659 724 789
Amps 2.43 2.71 3.00 3.30
-5
Lb/h 76.1 74.3 72.6 70.9
Btu/h 6680 6280 5900 5530 5160
Watts 607 676 745 814 883
Amps 2.48 2.79 3.11 3.43 3.76
0
Lb/h 84.5 82.6 80.8 79.0 77.3
Btu/h 7480 7040 6620 6220 5810
Watts 621 694 766 838 912
Amps 2.53 2.87 3.21 3.56 3.91
5
Lb/h 94.0 92.0 90.1 88.2 86.4
Btu/h 8370 7900 7440 6990 6550 6110 5680
Watts 636 711 786 862 940 1020 1100
Amps 2.59 2.95 3.31 3.68 4.05 4.44 4.84
10
Lb/h 105 102 100 98.5 96.5 94.6 92.6
Btu/h 9350 8840 8340 7850 7360 6880 6400
Watts 651 728 806 886 967 1050 1140
Amps 2.64 3.03 3.41 3.80 4.19 4.60 5.01
15
Lb/h 116 114 112 110 108 106 104
Btu/h 10400 9870 9330 8790 8260 7730 7210
Watts 666 745 826 909 994 1080 1170
Amps 2.70 3.11 3.51 3.92 4.33 4.75 5.18
20
Lb/h 129 126 124 122 120 118 116
Commentaires sur ces manuels